Description
General Data
- System power range: 10-40kVA
- Active Power/Frame: 10/15/20/30/40 kW
- Output power factor: 0.9 lead-0.6 lag
- Topology: online double conversion
- Ups type: stand alone, transformer based
- Parallel Configuration: Up to 6 units in parallel with Redundant Parallel Architecture (RPA)
Input
- Nominal input Voltage: 3 x 380/400/415 V + N
- Voltage tolerance: 340-460 V
- Input distortion THDi: <3%
- Frequency: 50/60 Hz
- Frequency range: 45-66 Hz
- Power factor: >0.99
- Walk-in / soft start: yes
Output
- Rated output voltage: 3 x 380/400/415 V + N
- Voltage tolerance: +/-1% static, +/-3% dynamic, +/-3% unbalanced load
- Voltage distortion THDU: <2% linear load, <3% nonlinear load (EN 62040)
- Frequency: 50/60 Hz
- Overload capability: 150% 1 min, 125% 10 min
- Output short Circuit capability: 2.7*In (Ph-N) / 4*In (Ph-Ph) for 200 ms
- Crest factor: <3:1
- Safety: IEC / EN 62040-1
- Electromagnetic Compatibility (EMC): IEC / EN 62040-2
- Performance: IEC / EN 62040-3
- Product certification: CE marking
- Manufacturing: ISO 9001
Efficiency
- Overall efficiency: Up to 92.3%
- In eco-mode (eBoost)Configuration: Up to 98%
Environment
- Storage temperature UPS: -25 °C +55 °C
- Operating temperature: 0-40 ˚C
- Humidity: Max. 95% (non-condensing)
- Altitude configuration: Up to 1000 m with no derating, at 1500 m:-2.5%/ 2000 m:-5%/ 2500 m:-7.5%/ 3000 m:-10% (EN/IEC 62040-3)
Communications
- HMI: Multilingual graphic display (LCD)
- Relay contractors: 6 voltage-free contacts for 27 programable alarms
- Input signals: EPO, Gen-ON (emergency power supply ON, n/o contact), 1 auxiliary signal (settable functionality)
- Communication ports: RS232, SNMP (optional)
Electrical/ Mechanical
- Degree of protection:IP20
- Color: 10-120 kVA RAL 9003 (white), 160-500 kVA RAL 9005 (black)
- Cable: entry Bottom (top optional)
- Back-feed protection: Built-in as standard
- Serviceability: Fully front serviceable
- Ventilation: From front to top
- Audible noise: <65 dB(A)
Batteries
- Type: VRLA batteries, vented lead-acid batteries, wet batteries, NiCd, flywheel
- DC floating voltage: 409-436 V
Standards
- Safety: IEC / EN 62040-1
- Electromagnetic compatibility (EMC): IEC / EN 62040-2
- Performance: IEC / EN 62040-3
- Product certification: CE marking
- Manufacturing: ISO 9001
Weight, Dimensions
- Weight (Kg): 290-420
- Dimensions (w × h × d (m)): 680x1450x800