Description
General features
99.9999% (6 nines) availability
- Decentralized parallel architecture
- No single point’s failure
- Redundant capacity (N+1) per frame
- Replace or add modules with no downtime
- Short mean time to repair
Low total cost of ownership
- Up to 96% true online efficiency ≥98%
- Unity power factor(kW=KVA)
- Low input harmonic distortion (THDi <3%)
- Small footprint/high power density (472kW/m2)
All in one solution
- Power range from 10 kW to 200 kW in a single frame
- Internal batteries for short autonomies and external battery cabinets for long autonomies
- User-friendly interface per module and system level
- Remote control and monitoring options available
Efficient service concept
- Simple power upgrade
- Fast maintenance
- Full front access
- Reduced spare parts needed
- System power range: 10-400kW
- National power per module: 10kW/20kW
- Nominal power/frame: 80kW
- Number of UPS modules: 1 to 4
- Output power factor: 1.0
- Topology: online double conversion
- Parallel configuration: up to 20 modules (up to 4 frames)
- UPS type: Modular (Decentralized Parallel architecture)
Input
- Nominal input voltage: 3*380/220V+N, 3×400/230V+N, 3×415/240V+N
- Voltage tolerance (referred to 3×400/230V): for load<100%(-20%, +15%), <80%(-25%, +15%), <60%(-35%, +15%)
- Input distortion THDi: ≤3%
- Frequency: 35-70Hz
- Power factor: 0.99
Output
- Rated output voltage: 3*380/220V+N, 3×400/230V+N, 3×415/240V+N
- Voltage distortion :< 1.5%
- Frequency: 50Hz or 60Hz
- Overload capability: 1 min.: up to 150%/ 10 min.: up to 125%
- Unbalanced load: 100 %( all three phases regulated independently)
- Crest factor: 3:1 (Load supported)
Efficiency
- Overall efficiency: Up to 96%
- In ECO mode configuration: 98%
Environment
- Storage temperature: -25°C to +70°C
- Operating temperature: 0°C to 40°C
- Altitude configuration: 1000m without derating
Communications
- LCD: yes (per module); system display optional (graphical touch screen display)
- LEDs: LED for notification and alarm
- Communication Ports: USB, RS-232, SNMP slot, potential-free contacts
Standards
- Safety: IEC/EN 62040-1
- Electromagnetic compatibility (EMC): IEC/EN 62040-2
- Performance: IEC/EN 62040-3
- Product certification: CE
- Manufacturing: ISO 9001:2015, ISO 14001:20 15, OHSAS18001
Weight, Dimensions
- Weight (with modules/without batteries): up to 168kg
- Dimension W×H×D (mm): 550×1135×775