ABB UPS SG Series 400-500 kVA

  • High Efficiency
  • High Performance and availability
  • Low cost of ownership
  • Easy installation and configuration flexibility
  • PurePulseTM – IGBT rectifier clean input
  • Robust rectifier for a wide input range
  • Programmable soft start
  • THDU
  • Overload capabilities
  • Voltage regulation
  • Short-circuit capability
  • Zig-zag output transformer
  • No derating required to supply resistive and capacitive loads (0.9)
  • Suitable for modern power supply application with unity or capacitive power factor, crest factor up to 3:1
Category: Tags: , ,

Description

General Data

  • System power range: 400-500kVA
  • Active Power/Frame: 360/450 kW
  • Output power factor: 0.9 lead-0.6 lag
  • Topology: online double conversion
  • Ups type: stand alone, transformer based
  • Parallel Configuration: Up to 6 units in parallel with Redundant Parallel Architecture (RPA)

Input

  • Nominal input Voltage: 3 x 380/400/415 V + N
  • Voltage tolerance: 340-460 V
  • Input distortion THDi: <3%
  • Frequency: 50/60 Hz
  • Frequency range: 45-66 Hz
  • Power factor:  >0.99
  • Walk-in / soft start: yes

Output

  • Rated output voltage: 3 x 380/400/415 V + N
  • Voltage tolerance: +/-1% static, +/-3% dynamic, +/-3% unbalanced load
  • Voltage distortion THDU: <2% linear load, <3% nonlinear load (EN 62040)
  • Frequency: 50/60 Hz
  • Overload capability: 150% 1 min, 125% 10 min
  • Output short  Circuit capability: 2.7*In (Ph-N) / 4*In (Ph-Ph) for 200 ms
  • Crest factor: <3:1
  • Safety: IEC / EN 62040-1
  • Electromagnetic  Compatibility (EMC): IEC / EN 62040-2
  • Performance:  IEC / EN 62040-3
  • Product certification: CE marking
  • Manufacturing: ISO 9001

Efficiency

  • Overall efficiency: Up to 94.2%
  • In eco-mode (eBoost)Configuration: Up to 98.7%

Environment

  • Storage temperature UPS: -25 °C +55 °C
  • Operating temperature: 0-40 ˚C
  • Humidity: Max. 95% (non-condensing)
  • Altitude configuration: Up to 1000 m with no derating, at 1500 m:-2.5%/ 2000 m:-5%/ 2500 m:-7.5%/ 3000 m:-10% (EN/IEC 62040-3)

Communications

  • HMI: Multilingual graphic display (LCD)
  • Relay contractors: 6 voltage-free contacts for 27 programable alarms
  • Input signals: EPO, Gen-ON (emergency power supply ON, n/o contact), 1 auxiliary signal (settable functionality)
  • Communication ports: RS232, SNMP (optional)

Electrical/Mechanical

  • Degree of protection:IP20
  • Color: 10-120 kVA RAL 9003 (white), 160-500 kVA RAL 9005 (black)
  • Cable: entry Bottom (top optional)
  • Back-feed protection: Built-in as standard
  • Serviceability: Fully front serviceable
  • Ventilation: From front to top
  • Audible noise: <69 dB(A)

Batteries

  • Type: VRLA batteries, vented lead-acid batteries, wet batteries, NiCd, flywheel
  • DC floating voltage: 409-436 V

Standards

  • Safety: IEC / EN 62040-1
  • Electromagnetic compatibility (EMC): IEC / EN 62040-2
  • Performance: IEC / EN 62040-3
  • Product certification: CE marking
  • Manufacturing: ISO 9001

Weight, Dimension

  • Weight (Kg): 2190-2470
  • Dimensions (w × h × d (m)): 1800x1900x950

Reviews

There are no reviews yet.

Be the first to review “ABB UPS SG Series 400-500 kVA”

Your email address will not be published. Required fields are marked *