FLUKE 435-II-INTL ADVANCED POWER QUALITY AND ENERGY ANALYZER

  • Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
  • Troubleshoot real-time: Analyze the trends using the cursors and zoom tools.
  • Automatic Trending: Every measurement is always automatically recorded, without any set-up.

Description

The Fluke 435-II products are designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing in your facility.

  • Troubleshoot Real-Time: Analyze the trends using the cursors and zoom tools.
  • Automatic Trending: Every measurement is always automatically recorded, without any set-up.
  • Logger Function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
  • Measure All Three Phases and Neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
  • PowerWave Data Capture: Capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics.
  • Power Inverter Efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
  • Energy Loss Calculator: Classic active and reactive power measurements, unbalance and harmonic power are quantified to pinpoint the energy loss costs.
  • Highest Safety Rating in the Industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
  • System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
  • View Graphs and Generate Reports: With included analysis software
Product Specifications
Volt Model Measurement Range Resolution Accuracy
Vrms (AC + DC) 1 V to 1000 V phase to neutral 0.01 V ±0.1% of nominal voltage1
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%
Vrms½ 0.1 V ±0.2% of nominal voltage
Vfund 0.1 V ±0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC) i430-Flex 1x  5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1mV/A 1x 5 A to 2000 A 1A ±0.5% ±5 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Apk i430-Flex 8400 Apk 1 Arms ±5%
1mV/A 5500 Apk 1 Arms ±5%
A Crest Factor (CF) 1 to 10 0.01 ±5%
Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts
1mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts
Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Hz
Fluke 434 @ 50 Hz Nominal 42.50 Hz to 57.50 Hz 0.01 Hz ±0.01 Hz
Fluke 434 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.01 Hz ±0.01 Hz
Power
Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ±0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 1000 V 0.1 V ±5%1
THD 0.0% to 100% 0.1% ±2.5%
Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts
THD 0.0% to 100% 0.1% ±2.5%
Watts % f or r 0.0% to 100% 0.1% ±n x 2%
Absolute Depends on clamp scaling and V nominal ±5% ±n x 2% ±10 counts
THD 0.0% to 100% 0.1% ±5%
Phase Angle -360° to +0° ±n x 1°
Flicker
Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%
Unbalance
Volts % 0.0% to 20.0% 0.1% ±0.1%
Amps % 0.0% to 20.0% 0.1% ±1%
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz
Relative V % 0% to 100% 0.10% ±0.4%
Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage
General Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Temperature -20°C ~ +60°C
Humidity +10°C ~ +30°C: 95% RH non-condensing
+30°C ~ +40°C: 75% RH non-condensing
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories

Reviews

There are no reviews yet.

Be the first to review “FLUKE 435-II-INTL ADVANCED POWER QUALITY AND ENERGY ANALYZER”

Your email address will not be published. Required fields are marked *