Description
- Features
The Fluke 435-II products are designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The measurement process and display of data is optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into tabular format such as the event data where the magnitude, duration and time stamping enable rapid correlation to the problems you are experiencing in your facility.
- Troubleshoot Real-Time: Analyze the trends using the cursors and zoom tools.
- Automatic Trending: Every measurement is always automatically recorded, without any set-up.
- Logger Function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
- Measure All Three Phases and Neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
- PowerWave Data Capture: Capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics.
- Power Inverter Efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
- Energy Loss Calculator: Classic active and reactive power measurements, unbalance and harmonic power are quantified to pinpoint the energy loss costs.
- Highest Safety Rating in the Industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
- System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
- View Graphs and Generate Reports: With included analysis software
Product Specifications | ||||
Volt | Model | Measurement Range | Resolution | Accuracy |
Vrms (AC + DC) | 1 V to 1000 V phase to neutral | 0.01 V | ±0.1% of nominal voltage1 | |
Vpk | 1 Vpk to 1400 Vpk | 1 V | 5% of nominal voltage | |
Voltage Crest Factor (CF) | 1.0 > 2.8 | 0.01 | ±5% | |
Vrms½ | 0.1 V | ±0.2% of nominal voltage | ||
Vfund | 0.1 V | ±0.1% of nominal voltage | ||
Amps (accuracy excluding clamp accuracy) | ||||
Amps (AC + DC) | i430-Flex 1x | 5 A to 6000 A | 1 A | ±0.5% ±5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±0.5% ±5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ±0.5% ±5 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±0.5% ±5 counts | |
Apk | i430-Flex | 8400 Apk | 1 Arms | ±5% |
1mV/A | 5500 Apk | 1 Arms | ±5% | |
A Crest Factor (CF) | 1 to 10 | 0.01 | ±5% | |
Amps½ | i430-Flex 1x | 5 A to 6000 A | 1 A | ±1% ±10 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±1% ±10 counts | |
1mV/A 1x | 5 A to 2000 A | 1 A | ±1% ±10 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±1% ±10 counts | |
Afund | i430-Flex 1x | 5 A to 6000 A | 1 A | ±0.5% ±5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±0.5% ±5 counts | |
1mV/A 1x | 5 A to 2000 A | 1 A | ±0.5% ±5 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±0.5% ±5 counts | |
Hz | ||||
Fluke 434 @ 50 Hz Nominal | 42.50 Hz to 57.50 Hz | 0.01 Hz | ±0.01 Hz | |
Fluke 434 @ 60 Hz Nominal | 51.00 Hz to 69.00 Hz | 0.01 Hz | ±0.01 Hz | |
Power | ||||
Watts (VA, var) | i430-Flex | max 6000 MW | 0.1 W to 1 MW | ±1% ±10 counts |
1 mV/A | max 2000 MW | 0.1 W to 1 MW | ±1% ±10 counts | |
Power Factor (Cos j/DPF) | 0 to 1 | 0.001 | ±0.1% @ nominal load conditions | |
Energy | ||||
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp scaling and V nominal | ±1% ±10 counts | |
Energy Loss | i430-Flex 10x | Depends on clamp scaling and V nominal | ±1% ±10 counts Excluding line resistance accuracy | |
Harmonics | ||||
Harmonic Order (n) | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 | |||
Inter-Harmonic Order (n) | OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 | |||
Volts % | f | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.1% |
r | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.4% | |
Absolute | 0.0 to 1000 V | 0.1 V | ±5%1 | |
THD | 0.0% to 100% | 0.1% | ±2.5% | |
Amps % | f | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.1% |
r | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.4% | |
Absolute | 0.0 to 600 A | 0.1 A | ±5% ±5 counts | |
THD | 0.0% to 100% | 0.1% | ±2.5% | |
Watts % | f or r | 0.0% to 100% | 0.1% | ±n x 2% |
Absolute | Depends on clamp scaling and V nominal | — | ±5% ±n x 2% ±10 counts | |
THD | 0.0% to 100% | 0.1% | ±5% | |
Phase Angle | -360° to +0° | 1° | ±n x 1° | |
Flicker | ||||
Plt, Pst, Pst (1 min) Pinst | 0.00 to 20.00 | 0.01 | ±5% | |
Unbalance | ||||
Volts % | 0.0% to 20.0% | 0.1% | ±0.1% | |
Amps % | 0.0% to 20.0% | 0.1% | ±1% | |
Mains Signaling | ||||
Threshold Levels | Threshold, limits and signaling duration is programable for two signaling frequencies | — | — | |
Signaling Frequency | 60 Hz to 3000 Hz | 0.1 Hz | ||
Relative V % | 0% to 100% | 0.10% | ±0.4% | |
Absolute V3s (3 second avg.) | 0.0 V to 1000 V | 0.1 V | ±5% of nominal voltage | |
General Specifications | ||||
Case | Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 | |||
Display | Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated | |||
Memory | 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) | |||
Real-Time Clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture | |||
Environmental | ||||
Operating Temperature | 0°C ~ +40°C; +40°C ~ +50°C excl. battery | |||
Storage Temperature | -20°C ~ +60°C | |||
Humidity | +10°C ~ +30°C: 95% RH non-condensing +30°C ~ +40°C: 75% RH non-condensing +40°C ~ +50°C: 45% RH non-condensing |
|||
Maximum Operating Altitude | Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V Maximum storage altitude 12 km (40,000 ft) |
|||
Electro-Magnetic-Compatibility (EMC) | EN 61326 (2005-12) for emission and immunity | |||
Interfaces | Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery | |||
Warranty | Three years (parts and labor) on main instrument, one year on accessories |
Reviews
There are no reviews yet.