Description
General data | |
System power range | 1 kVA – 10 kVA |
UPS output rated PF | 0.8 (1-3kVA), 0.9 (6-10 kVA) |
Max. no of parallel frames | Up to 4 units |
Wiring | 1ph + N + PE |
UPS type | Stanalone tower |
Topology | True online double conversion |
Input | |
Nominal input voltage | 200, 208, 220, 230, 240 VAC |
Voltage range | 176 – 276 VAC (load dependent) |
Frequency range | 45 – 55 Hz for 50 Hz systems
55 – 66 Hz for 60 Hz systems |
Current THD at 100% load | ≤5% |
Power Factor at 100% load | ≥0.99 |
Output | |
Rated output voltage | 208, 220, 230, 240 VAC |
Voltage THD (with linear load) | ≤3% (1-3kVA), ≤2% (6-10kVA) |
Frequency | 50 or 60 Hz (selectable) |
Efficiency | |
Online double conversion | Up to 92% |
Eco-mode | Up to 96% |
Communications | |
User interface | LCD |
Communication ports | USB, RS-232, SNMP slot, potential-free contacts (optional) |
Software | Monitoring and shutdown software available as option |
Compliancy | |
Safety | IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 |
Performance | IEC/EN 62040-3 |
Manufacturing | ISO 9001:2008, ISO 14001:2004 |
Technical specifications are subject to change without notice.