AMB ON PLUS 33 (200KL)

  • DSP technology guarantees high performance
  • Output power factor 1.0
  • Pluggable power module design
  • Front access design for easy maintenance
  • Active power factor correction in all phases
  • Emergency power off function (EPO)
  • Dual AC inputs
  • Parallel operation up to 4 units with common battery
  • Power walk-in function while parallel operations
  • Generator compatible
  • Adjustable battery numbers
  • Maintenance bypass available
  • 3-stages extendable charging design for optimized battery performance
  • Optional isolation transformer offers full isolation and complete common mode noise rejection

Description

  • Phase: 3 phases in/ 3 phases out
  • Capacity: 200KVA/200KW
  • Parallel capability: 4

Input

  • Nominal voltage: 3×360/380/400/415 VAC (3Ph+N)
  • Voltage range: 110-300 VAC @ 50% load; 176-276 VAC @ 100% load
  • Frequency range: 40~70 Hz
  • Power factor: ≤99 @ 100% load
  • Harmonic distortion (THDi): < 4% at full linear load

Output

  • Output Voltage: 3×360*/380*/400/415 VAC (3Ph+N)
  • AC voltage Reputation: ±1%
  • Frequency range (synchronized range): 46~54Hz or 56~64Hz
  • Frequency range (batt.mode): 50/60 Hz ± 1%
  • Current crest ratio: 3:1 (max.)
  • Harmonic distortion: ≤2% THD (Linear load); ≤5% THD (non-linear load)
  • Transfer Time: AC mode to battery mode: 0
    • Inverter to bypass: 0
  • Wave form (Batt.mode): Pure sine wave
  • Overload capacity: 100-110% for 60min, 111-125% for 10mins, 126-150% for 1 min ;>150% immediately shutdown

Bypass

  • Nominal voltage: 3×360/380/400/415 VAC (3Ph+N)
  • Voltage range: 305VAC-457VAC
  • Frequency range (Synchronized range):46~54Hz or56~64Hz
  • Overload capability: >130% 1 minute (default); continuously working until breaker protection (optional)

Efficiency

  • AC Mode: 95.5%
  • ECO Mode: 98.5%
  • Battery Mode: 94.5%

Battery

  • Standard model battery type: N/A
  • Standard model numbers: N/A
  • Standard model charging current (max): N/A
  • Standard model charging voltage: N/A
  • Long-run Battery type: depending on applications
  • Long-run numbers: 32-40 pcs (Adjustable)
  • Long-run charging (max): 3-54 (Adjustable)
  • Long-run charging voltage: +/-13.65V*N (N=16~20)

Indicator

  • Touch color LCD panel: UPS status, load level, battery level, Input/output voltage, discharge timer, and fault conditions

Physical

  • Standard model dimensions: N/A
  • Standard model net weight (Kgs): N/A
  • Long-run model dimensions (D×W×H) (mm): 974×600×1600
  • Long-run net weight (Kgs): 345

Environment

  • Operating temperature: 0-40°C
  • Operating humidity: <95% and non-condensing
  • Altitude**: 0-1000m at full load
  • Noise level: less than 75 dB @1 meter

Management

  • Smart RS-232/USB: supports windows family, Linux and MAC
  • Optional SNMP: power management from SNMP manager and web browser