| General data | |
| System power range | 160 kW – 5000 kW |
| UPS frame rated power | 160 / 200 / 250 / 300 / 400 / 500 kW |
| UPS output rated PF | 1.0 |
| Max. no of parallel frames | Up to 10 units |
| Wiring | 3ph + N + PE |
| UPS type | Standalone tower |
| Topology | True online double conversion |
| Input | |
| Nominal input voltage | 220/380, 230/400, 240/415 VAC |
| Voltage range | 150/204 – 264/460 VAC (load dependent) |
| Frequency range | 35-70 Hz |
| Current THD at 100% load | ≤ 3.5-4 % |
| Power Factor at 100% load | 0.99 |
| Output | |
| Rated output voltage | 220/380, 230/400, 240/415 VAC |
| Voltage THD (with linear load) | <2% |
| Frequency | 50 or 60 Hz (selectable) |
| Efficiency | |
| Online double conversion | Up to 96% |
| Eco-mode | 99% |
| Communications | |
| User interface | Graphical touch screen (optional on 60-200 kW) LCD + mimic diagram (on 60-200 kW only) |
| Communication ports | USB, RS-232, SNMP slot, potential-free contacts |
| Software | Monitoring and shutdown software available as option |
| Compliancy | |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| Manufacturing | ISO 9001:2008, ISO 14001:2004 |
Technical specifications are subject to change without notice.