PowerValue 11T G2 (ABB)

Single-phase UPS from 1 kVA to 10 kVA (ABB)

ABB’s PowerValue 11T G2 is a single-phase in/out, double conversion online uninterruptible power supply (UPS) that guarantees up to 10 kW per single UPS of clean, reliable power for your critical single-phase applications. As well as maintaining power to your server room, advertising display, turnstiles, lab equipment, transportation signaling systems, ATM or vending machine, the PowerValue 11T G2 also conditions incoming power to eliminate spikes, swells, sags, noise and harmonics.

Featuring voltage and frequency independent (VFI) topology, the tower-only PowerValue 11T G2 saves costs by minimizing energy losses with its double conversion efficiency of up to 95 percent (up to 98% in ECO mode). Two or three units can be connected in parallel to boost power delivery to a maximum of 30 kW or to provide redundancy.

Simple to install or maintain, inexpensive to run and with the most compact online UPS footprint available on the market, the PowerValue 11T G2 provides stable, regulated, transient-free, pure sine wave AC power with extremely tight output voltage regulation. All units can be fitted with up to four external battery modules (EBMs) to extend runtime to well over two hours. Each EBM is dedicated to its corresponding UPS and setup is easily accomplished via the LCD menu.

Description


GENERA DATA
UPS frame rated power 1 / 2 / 3 / 6 / 10 kVA
UPS module rated power
UPS output rated PF 0.9 – 1.0
Max no of parallel frames Up to 3 units (model dependent)
Max no of parallel modules across frames
Max system power 30 kW
Wiring 1-ph + N + PE
UPS type Standalone tower
Topology Online double conversion
INPUT
Nominal input voltage 220 / 230 / 240 VAC (1 – 3 kVA)
208 / 220 / 230 / 240 VAC (6 – 10 kVA)
Voltage range 100 – 300 VAC (1 – 3kVA)
100 – 276 VAC (6 – 10 kVA)
Frequency range 45 – 55 Hz / 54 – 66 Hz
45 – 55 Hz / 54 – 66 Hz (extendable to 40~70 Hz at load < 60%)
Current THD at 100% load 5% with full resistive load (1 – 3 kVA)
<3% with full resistive load (6 – 10 kVA)
Power Factor at 100% load ≥0.99 (1 – 3 kVA)
≥0.995 (6 – 10 kVA)
OUTPUT
Rated output voltage (load dependent) 220 / 230 / 240 VAC (1 – 3 kVA)
208 / 220 / 230 / 240 VAC (6 – 10 kVA)
Voltage THD (with linear load) <2% linear load, <6% non linear load (1 – 3 kVA)
<1% linear load, <5% non linear load (6 – 10 kVA)
Rated frequency 50 or 60 Hz
EFFICIENCY
Double conversion Up to 95%
Eco-mode Up to 98%
COMMUNICATIONS
User interface LCD
Communication ports SNMP; ModBus; AS400; Environmental monitoring sensor probe
Software Monitoring and shutdown software available as option