Description
| General data | |
| System power range | 10 kVA – 1000 kVA |
| UPS frame rated power | 10/9-15/13.5-20/18-25/22.8-30/27-40/36-50/45 kVA/kW |
| UPS output rated PF | 0.9 |
| Max. no of parallel frames | Up to 20 units |
| Wiring | 3ph + N + PE |
| UPS type | Standalone tower |
| Topology | True online double conversion |
| Input | |
| Nominal input voltage | 220/380, 230/400, 240/415 VAC |
| Voltage range | 150/204 – 264/460 VAC (load dependent) |
| Frequency range | 35-70 Hz |
| Current THD at 100% load | ≤3% |
| Power Factor at 100% load | ≥0.99 |
| Output | |
| Rated output voltage | 220/380, 230/400, 240/415 VAC |
| Voltage THD (with linear load) | <2% |
| Frequency | 50 or 60 Hz (selectable) |
| Efficiency | |
| Online double conversion | Up to 95.5% |
| Eco-mode | 98% |
| Communications | |
| User interface | LCD + mimic diagram |
| Communication ports | USB (optional), RS-232, SNMP slot, potential-free contacts (optional) |
| Software | Monitoring and shutdown software available as option |
| Compliancy | |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| Manufacturing | ISO 9001:2008, ISO 14001:2004 |
Technical specifications are subject to change without notice.

Reviews