Description
| General data | |
| UPS frame rated power | 20 – 120 kVA (3ph); 20 – 80 kVA (1ph) |
| UPS module rated power | 50 – 40 kVA |
| UPS output rated PF | 1.0 |
| Max no of parallel frames | 2 (Redundancy) |
| Max no of parallel modules across frames | 6 |
| Max system power | 120 kVA |
| Wiring | 3ph + N + PE (3ph); 1ph + N + PE (1ph) |
| UPS type | Modular (DPA) |
| Topology | Online double conversion |
| Input | |
| Nominal input voltage | 400/230 VAC, others on request |
| Voltage range | For loads <100% (-15%, +10%), <80% (-20%, +10%), <60% (-25%, +10%) |
| Frequency range | 50 or 60 Hz (selectable) |
| Current THD at 100% load | ≤ 4% |
| Power Factor at 100% load | 0.99 |
| Output | |
| Rated output voltage (load dependent) |
400/230 VAC (3ph); 230 VAC (1ph) |
| Voltage THD (with linear load) | < 2% |
| Rated frequency | 50 or 60 Hz (selectable) |
| Efficiency | |
| Double conversion | Up to 96% |
| Eco-mode | 98,5% |
| Communications | |
| User interface | System graphical display (HMI) + LCD panel UPS Module |
| Communication ports | SNMP; ModBus; potential free contacts slot, potential free contacts |
| Software | Monitoring and shutdown software available as option |
Technical specifications are subject to change without notice.