Description
General features
High reliability
- Double conversion topology protects the load from all input disturbances
- Parallel able up to three units (6-10k only) to provide system redundancy
- User replaceable batteries
- Wide input voltage tolerance
Low cost of ownership
- Scalable runtime
- High operating efficiency
- Low installation and upgrading costs
- Compact design
- Output power factor of 1.0 (6-10 kVA only)
Flexible design
- Multiple connectivity options
- Each UPS can be connected with up to four parallel battery modules for extended runtime
- Adjustable DC voltage and battery charger current
- Extended backup time models available
- Best power density available in the market Segment
Efficient service concept
- Integrated manually operated maintenance bypass switch (6-10 kVA only)
- Easy setup and maintenance (plug and play)
- User-friendly display
Remote monitoring options
- Output rated power: 900 W
- Output power Factor: 0.9
- Topology: Online double conversion
- Parallel configuration: No
- Inbuilt batteries: Yes/No
Input
- Nominal input voltage: 220/230/240 VAC
- Input voltage tolerance: 100-300 VAC (load dependent)
- Input current THDi: 5% with full resistive load
- Frequency range: 45-55Hz / 54-66 Hz
- Power Factor: ≥99
Output
- Rated output voltage: 220/230/240 VAC
- Voltage tolerance: ±1 %( referred to 230V)
- Voltage distortion: ≤2% linear load, <6% non-linear load
- Overload capacity (linear load) on inverter: 60s: 106-130% load, 10s: 131-150% load, 300ms: ≥ 150% load
- Nominal frequency: 50 or 60 Hz
- Crest factor: 3:1 (load supported)
Efficiency
- Overall system efficiency: Up to 89%
- In Eco-mode: up to 97.5%
Environment
- Protection rating: IP20
- Storage temperature: UPS: -25°C to 60°C; Batteries: 0°C to 35°C
- Operating temperature: 0°C to 40°C
- Relative humidity: 0% to 95%
- Altitude (above sea level): 1000m without derating
Batteries
- Type: VRLA (valve regulated lead-acid)
- Inbuilt batteries: 2×4Ah (B)
- Charging current: 1.5A/3-6A adjustable
- Recharge time (inbuilt batteries): 4h to 90%
Communications
- User interface: LCD display
- Optional communication cards: SNMP; Modbus; AS400; Environmental monitoring sensor probe
Standards
- Safety: IEC/EN 62040-1
- EMC: IEC/EN 62040-2
- Performance: IEC/EN 62040-3
- Manufacturing: ISO 9001:2015, ISO 14001:2015, OHSAS 18001
Weight, Dimensions
- Weight: 9.2/ 3.9 kg
- Dimensions (W×H×D): 144x228x356 mm, 102x228x346mm
Reviews