Description
Specification
Capacity: 6000VA /6000W
Input
Nominal Voltage: 208/220/230/240Vac
Voltage range: 110~300Vac
Nominal Frequency: 50Hz/60Hz (Auto Sensing)
Frequency Range: (40~70)Hz
Power Factor: 0.99
Output
Nominal Voltage(Batt. mode): 208/220/230/240 Vac
Voltage Regulation: ± 1 %
Nominal Output Frequency: 50/60Hz
Frequency Range (Batt.): ± 0.05Hz
Waveform: Pure Sine Wave
THDv: ≤ 2% @ linear load, ≤5%@non-linear load
Current Crest Ratio: 3:1
Transfer Time: 0 ms
Surge Protection: 600 Joule
Overload Protection:
Line Mode: 105%-125%, transfer to bypass after 10min; 125%-150%, transfer to bypass after 1min; >150%, transfer to bypass after 10s; >170%, transfer to bypass immediately
Battery Mode: 105%-125%, shut down after 2mins; 125%-150%, shut down after 30s; >150% shut down immediately
Bypass Mode: 125%-150% cut off output and alarm continually after 1 min; 150%, cut off output and alarm continually after 10s; >170%, cut off output and alarm continually after 1s;
Battery
Voltage: 240V
Type: Depends on external batteries
Total Battery Quantity: Depends on external batteries
Recharge Time (to 90%): Depends on external batteries
Charging Current: 4A
Efficiency
Efficiency (Inverter Mode): 92%
Efficiency (Batt. Mode): 90%
ECO Mode: 96%
Indicators
Display: LCD
Alarm: Batt. Mode, low battery, overload, fault, etc.
Interface
RS232: Yes
HID Compliant USB port: Yes
SNMP: Yes
EPO: Yes
Management
Parallel Operation: Up to 4
Auto Recharge: Yes
Auto Restart: Yes
Maintenance Switch: Yes
Power Management Software: Yes
Physical
Dimension (W x H x D) (mm): 260 x 708 x 550
Net Weight (kg): 25
Environment
Operating Humidity: 0-90% non-condensing
Operating Temperature: 0-40°C
Noise Level: <60 dB
Note: All specifications are subject to change without notice