AMB-ON-PLUS-6000-RT

Key Features

  • True double-conversion
  • Output power factor 1
  • Output voltage regulation < 1%
  • 50Hz/60Hz frequency converter mode
  • Programmable power management outlets
  • Hot swappable battery design
  • ECO mode energy saving
  • Provides over voltage cut-off protection and surge immunity by MOV for full time equipment protection
  • High power factor charger up to 8A/12A capacity with very low ripple current when charging battery
  • Low input THDi to reduce power system pollution
  • Adjustable charging current via LCD panel
  • Optional HID Power Device USB Port

Description

Model: AMB-ON-PLUS-6000-RT

Specification

  • Phase: Single phase with ground
  • Capacity:6000 VA / 6000 W

Input

  • Nominal Voltage: 208/220/230/240 VAC
  • Voltage range: 110~300VAC ± 3 % at 50% load
    176~300VAC ± 3 % at 100% load
  • Frequency Range:46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
  • Power Factor:≥ 0.99 @ full load
  • Harmonic Distortion (THDi): < 4% @100% Load, < 6% @50% Load

Output

  • Output Voltage(Batt. mode): 208*/220/230/240 VAC
  • AC Voltage Regulation (Batt. Mode): ± 1 %
  • Frequency Range (Synchronized Range): 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
  • Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
  • Harmonic Distortion: ≤ 1 % THD (Linear Load) ; ≤ 4 % THD (Non-linear Load)
  • Waveform: Pure Sinewave
  • THDv: ≤ 3% @ linear load, ≤5%@non-linear load
  • Current Crest Ratio: 3:1 (max.)
  • Transfer Time: 0 for AC Mode to Batt. Mode, 0 for Inverter to Bypass

Efficiency

  • AC Mode: ≥ 94% @ full charged battery
  • Battery Mode: ≥ 92%
  • ECO Mode: ≥ 98.5% @ full charged battery

Battery

  • Model 6000L
  • Standard Model 
  • Type: 12 V/ 9 Ah 
  • Total Battery Quantity:16 
  • Total Battery Quantity: 20
  • Recharge Time: 9 hours recover to 90% capacity for internal battery@ 2A charging current
  •  Charging Voltage: 218.4 VDC ± 1%
  • Charging Voltage: 273 VDC ± 1%
  • Charging Current: 1.0 A
  • Long-run Model
  •  Type: Depending on applications
  • Total Battery Quantity: 16-20**
  • Charging Voltage:(13.65VDC x battery number) ± 1%
  • Charging Current: 4.0 A

Indicators

  • LCD Display: UPS status, Load level, Battery level, Input/output voltage, Discharge timer, and Fault condition

Alarm

  • Battery Mode: Sounding every 4 seconds
  • Low Battery: Sounding every second
  • Overload: Sounding twice every second
  • Fault: Continuously sounding

Physical

Standard Model

  • Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U] Battery Pack:715x438x88 [2U]
  • Net weight : UPS Unit: 17
    Battery Pack: 48
  • Dimension (W x H x D) (mm): UPS Unit: 610x438x88 [2U] Battery Pack:600x438x133 [3U]
  • Net weight : UPS Unit: 17
    Battery Pack: 57

Environment

  • Operating Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
  • Noise Level: Less than 55dB @ 1 Meter

Management

  • Smart RS-232/USB: Supports Windows ® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC
  • Optional SNMP: Power management from SNMP manager and web browser
  • Power Management Software: Yes

Standard

  • EMC/safety: EMC EN62040-2 C2 for CE models