Description
- Capacity: 2700W/2400W
Input
- Nominal voltage: 220-240Vac
- Voltage range: 80-300Vac
- Nominal frequency: 50Hz/60Hz
- Frequency range: 40-70Hz
- Power factor: 0.99
- Output
- Nominal voltage (batt mode): 208/220/230/240Vac
- Voltage regulation: ±1%
- Nominal output frequency: 50Hz/60Hz
- Frequency range (batt): 50Hz/60Hz±5%
- Waveform: Pure sine wave
- THDv: ≤3% @ linear load, ≤5%@ non-linear load
- Current crest ratio: 3:1
- Transfer time: 0ms
- Overload protection: line mode: 105%-110% warning, transfer to bypass after 10 min; 110%-130% warning, transfer to bypass after 1 min ;> 130% transfer to bypass after 3s.
- Battery mode: 105%-110% warning, shut down after 10 min; 110%-130% warning, shut down after 1 min ;> >130% shut down after 3s.
- Bypass mode: 110%-120% warning, shut down after 30 mins; 120%-130% warning, shut down after 10 min ;> 130% shut down after 1 min.
Battery
- Model name: 3000
- Battery voltage: 72V
- Battery type: 12V/9Ah
- Total battery quantity: 6
- Recharge time (to 90%): 4Ah
- Charging current: 1.5A
Efficiency
- Inverter mode: 91%
- mode:88%
- ECO mode: 96%
- Indicators
- Display: LCD
- Alarm: yes
Interface
- RS 232: yes
- HID complaint USB Port: yes
- EPO: yes
- SNMP: yes
Management
- Auto recharge: yes
- Auto restart: yes
- Power management software: yes
Physical
- Dimensions (W×H×D) (mm): 196×342×416
- Net weight (kg): 21.3 and 26.7
Environment
- Operating humidity: 0.90% non-condensing
- Operating temperature: 0-40°C
- Noise level:<45 dB
Reviews
There are no reviews yet.