AMB ON PLUS 33 (10000 (L)*)

  • DSP technology guarantees high performance
  • Output power factor 1
  • Adapting the latest silicon carbide diodes to enhance the system efficiency
  • Dual inputs
  • Very powerful charger to shorten the recharge time
  • Adjustable charging current
  • Parrallel up to 6 units with common battery pack
  • 5”colour touch type LCD display
  • Optional programmable relay dry contact card
  • Voice warning/error code notice
  • High overload capability
  • Adjustable battery design
  • Dynamic password feature optimizes service performance
  • Power walk-in function

Description

  • Phase: 3-phase in / 3-phase out
  • Capacity: 10kVA/10KW
  • Parallel capability: up to 6 units in parallel

Input

  • Nominal voltage: 3×380/400/415 VAC (3Ph+N)
  • Voltage range: -30%~+20%
  • Frequency range: 40~70 Hz
  • Power factor: @ 0.99 @ 100% load
  • Harmonic distortion (THDi) <3% at full linear load

Output

  • Output voltage: 3×360*/380/400/415 VAC (3Ph+N)
  • AC voltage Regulation (Batt. Mode):±1%
  • Frequency range (synchronized range): 46~54Hz or 56~64Hz
  • Frequency range (Batt. Mode): 50/60 Hz ±1%
  • Current crest ratio: 3:1 (max)
  • Harmonic distortion: @1% THD (Linear Load); @3% THD (non-linear load)
  • Transfer time: AC mode to Batt. Mode: 0
    • Inverter to bypass: 0
  • Waveform (Batt. Mode): Pure sine wave
  • Overload capability: 100-110% for 60 min, 111-125% for 10 mins, 126%~150% for 1 min ;> 150% or 400ms

Bypass:

Nominal voltage: 3×380/400/415VAC (3Ph+N)

Voltage range: -30%~+20 %( Adjustable)

Frequency range (synchronized range): 46~54Hz or 56~64Hz

Overload capability: >130% 1 minute (default). Continuously working until breaker protection (optional)

Efficiency

  • AC mode: 96.0%
  • ECO mode: 99.0%
  • Battery mode: 96.0%

Battery

  • Standard model battery type: 12 V/9 Ah
  • Standard model number: (10+10) pcs
  • Standard model typical recharge type: 9 hours recover to 90% capacity
  • Standard model charging current (max): 1A~12A (Adjustable)
  • Standard model charging voltage: +/-136.5 VDC±10%
  • Long-run model Battery type: Depending on the application
  • Long-run model numbers: +/- 10 pcs
  • Long-run model charging current (max): 1A~12A (Adjustable)
  • Long-run model charging voltage: +/-136.5 VDC±10%

Indicators

  • LCD panels: UPS status, Load level, Battery level, Input/output voltage, Discharge timer, and Fault conditions

Physical

  • Standard model Dimension (D×W×H) (mm):630×250×826
  • Standard model net weight (kgs):124
  • Long-run model dimension (D×W×H)(mm): 630 x 250 x 826
  • Long-run net weight: 28

Environment

  • Operation temperature: 0-40°C
  • Operation humidity: <95% and non-condensing
  • Altitude**: 0 ~ 1500m at full load
  • Noise level: Less than 60 dB @1 Meter

Management

  • Smart RS-232/USB: Supports Windows* 2000/2003/XP/Vista/2008, Windows* 7/8/10, Linux and MAC
  • Optional SNMP: Power management from SNMP manager and web browser