Description
| General data | |
| System power range | 10 kVA – 80 kVA |
| UPS frame rated power | 10 / 20 kVA |
| UPS output rated PF | 0.9 |
| Max. no of parallel frames | Up to 4 units |
| Wiring | 1ph or 3ph + N + PE (selectable) |
| UPS type | Standalone tower |
| Topology | True online double conversion |
| Input | |
| Nominal input voltage | 220/380, 230/400, 240/415 VAC |
| Voltage range | 1-ph 110 – 276 VAC 3-ph 190 – 486 VAC |
| Frequency range | 45 – 55 Hz for 50 Hz systems
55 – 65 Hz for 60 Hz systems |
| Current THD at 100% load | ≤5% |
| Power Factor at 100% load | ≥0.99 |
| Output | |
| Rated output voltage | 220, 230, 240 VAC |
| Voltage THD (with linear load) | ≤2% |
| Frequency | 50 or 60 Hz (selectable) |
| Efficiency | |
| Online double conversion | Up to 93% |
| Eco-mode | Up to 97% |
| Communications | |
| User interface | LCD + LEDs |
| Communication ports | USB, RS-232, SNMP slot, potential-free contacts (optional) |
| Software | Monitoring and shutdown software available as option |
| Compliancy | |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| Manufacturing | ISO 9001:2008, ISO 14001:2004 |
| RoHS | IEC/EN 50581:2012 |
Technical specifications are subject to change without notice.