Description
Features
- Dedicated key for each test for Ãone-touchà testing
- Pre-set pass/fail levels to save time
- Large backlit display for easy reading
- Single mains socket for appliance connection
- Separate IEC socket for easy mains/extension lead testing
- Detachable test leads for quick field replacement
- Integral carrying handle
- USB port for data transfer
- Integral QWERTY keyboard for rapid data entry
- Additional USB memory capability for back-up data storage and transfer to PC
- Large backlit graphics display
- Pre-set; auto-test sequences for user convenience
- Integral site; location and description codes for faster data processing
- Memory review facility for more on-site control
- USB port for data transfer
Specifications | ||
Test specifications | The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75% RH. | |
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. | ||
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2. | ||
Power-on test | The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency. | |
Display range | 90 V to 264 V | |
Accuracy at 50 Hz | ±(2% + 3 counts) | |
Resolution | 0.1 V | |
Input impedance | > 1 MΩ // 2.2 nF | |
Maximum input mains voltage | 264 V | |
Earth bond test (Rpe) | Display Range | 0 to 19.99 Ω |
Accuracy (after bond test zeroing) | ±(5% + 4 counts) | |
Resolution | 0.01 Ω | |
Test current | 200 mA AC -0% +40% into 1.99 Ω 10 A AC ±20% into 25 mΩ at 230 V |
|
Open circuit voltage | > 4 V AC, < 24 V AC | |
Bond test zeroing | can subtract up to 1.99 Ω | |
Insulation test (Riso) | Display range | 0 to 299 MΩ |
Accuracy | ±(5% + 2 counts) from 0.1 to 300 MΩ | |
Resolution | 0.01 MΩ (0 to 19.99 MΩ) 0.1 MΩ (20 to 199.9 MΩ) 1 MΩ (200 to 299 MΩ) |
|
Test voltage | 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0% +25% at 250 kΩ load | |
Test current | > 1 mA at 500 kΩ load, < 15 mA at 0 Ω | |
Auto discharge time | < 0.5 s for 1 μF | |
Max. capacitive load | Operational up to 1 μF | |
Touch current test | Display range | 0 to 1.99 mA AC |
Accuracy | ±(4% + 2 counts) | |
Resolution | 0.01 mA | |
Internal resistance (via probe) | 2 kΩ | |
Measuring method | Probe* | |
Substitute leakage current test | Display range | 0 to 19.99 mA AC |
Accuracy | ±(2.5% + 3 counts) | |
Resolution | 0.01 mA | |
Test Voltage | 100 V AC ±20% | |
Load/leakage test: load current | Display range | 0 A to 13 A |
Accuracy | ±(4% + 2 counts) | |
Resolution | 0.1 A* | |
Load/leakage test: load power | Display range 230 V Mains | 0.0 VA to 3.2 kVA |
Accuracy | ±(5% + 3 counts) | |
Resolution | 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)* | |
Load/leakage test: leakage current | Display range | 0 to 19.99 mA |
Accuracy | ±(4% + 4 counts) | |
Resolution | 0.01 mA* | |
PELV test | Accuracy at 50 Hz | ±(2% + 3 counts) |
Overload protection | 300 V rms | |
Warning threshold | 25 V rms | |
RCD test: trip current | Operational error | ±10% |
Nominal | 30 mA | |
Accuracy | ±5% | |
RCD test: trip time | Standard requirement | 61557 Part 6; tolerance of rated test current 0% to +10% |
Operational error | ±10% | |
RCD type | AC general-purpose 30 mA | |
Display range | 310 ms | |
Resolution | 0.1 ms | |
Accuracy | 3 ms | |
Trip time limit at 100% (30 mA) | 300 ms | |
Trip time limit at 500% (150 mA) | 40 ms | |
*The appliance under test is energized at mains potential. |
Environmental specifications | |
Operating temperature | 0 to 40 °C |
Relative humidity | Non condensing <10 °C |
95% from 10 to 30 °C | |
75% from 30 to 40 °C |
Safety specifications | |
Safety rating | Complies with EN61010-1 3rd edition |
CAT II, 300 V, pol 2 |
Mechanical and general specifications | ||
Size (L x W x H) | 200 x 275 x 114 mm | |
Weight | 3.13 kg | |
Power supply | 230 V +10% -15%, 50 Hz ±2 Hz or (6500-2 only: 110V +10% -15%,50 Hz ±2 Hz) | |
Power consumption (tester) | 13 W typical (idle) 60 W max. during 25A Bond test |
|
Storage | Temperature | -10 to 60 °C |
Corrosion | 70 °C @ 95% RH for 5 days max. | |
Operating altitude | 0 up to 2000 m | |
Sealing | IP-40 (enclosure), IP-20 (connectors) | |
EMC | Complies with EN61326-1, portable | |
EMI Immunity | 3 V/m |